2026-02-06
A frequency drive (VFD) controls motor speed and torque by varying output frequency and voltage, delivering smoother starts, tighter process control, and large energy savings on variable-torque loads. For pumps and fans, dropping speed by 20% can cut shaft power demand by roughly ~50% due to the affinity laws (power ≈ speed³), while also reducing mechanical stress and maintenance.
A frequency drive rectifies incoming AC to DC, then inverts it back to AC at a commanded frequency. Motor speed is primarily set by frequency, while voltage and control algorithms regulate torque and stability.
Most applications fall into two behavior types: variable torque (fans/pumps) and constant torque (conveyors/extruders). Matching the drive’s control mode to the load improves low-speed torque, speed holding, and efficiency.
| Control method | Best for | Typical strengths | Watch-outs |
|---|---|---|---|
| V/Hz (scalar) | Fans, pumps, simple speed control | Simple setup, stable at mid/high speeds | Weaker low-speed torque, slower response |
| Sensorless vector | Conveyors, mixers, general purpose | Better low-speed torque and speed regulation | Needs accurate motor data, can be noisy if mis-tuned |
| Closed-loop vector (encoder) | Hoists, winders, precise low-speed control | High torque at 0 speed, tight regulation | Extra hardware, wiring, commissioning complexity |
Correct sizing is driven by motor full-load current (FLA) and the load’s overload demands, not only horsepower/kW. Start with the motor nameplate, then apply the application’s duty requirements.
If a 400V, 30kW motor has a nameplate FLA of ~56A (typical range depends on efficiency and power factor), choosing a drive with 60–70A continuous rating is often appropriate for fan/pump duty. For a conveyor with heavy starts, stepping up to a drive that can sustain higher overload may prevent trips during acceleration.
Most “mystery” VFD issues trace back to grounding, cable routing, or incorrect motor lead practices. Good installation reduces EMI, protects motor insulation, and improves control accuracy.
A VFD output is a PWM waveform, which can increase bearing currents and insulation stress in certain setups. Mitigation can include proper grounding, insulated bearings (when specified), common-mode chokes, and output filtering—especially with older motors or very long cable runs.
Entering accurate motor nameplate data and running the drive’s motor identification routine are the two highest-impact setup steps for stable torque production and fewer trips, especially in vector modes.
For pressure control, the drive can adjust speed to hold a setpoint. A practical starting approach is modest proportional gain and slow integral action, then refine based on response:
If the drive trips on overcurrent during acceleration, increase accel time or reduce starting load. If it trips on overvoltage during decel, extend decel time or add dynamic braking. For high-inertia loads, braking hardware often turns an unstable stop into a controlled one.
Frequency drive motor control is most financially compelling on variable-torque loads. The affinity laws provide a quick estimate: flow ∝ speed, head ∝ speed², and power ∝ speed³. That means small speed reductions can produce large kW reductions.
If a fan uses 30 kW at 100% speed, then at 80% speed the estimated shaft power is 30 × 0.8³ = 30 × 0.512 ≈ 15.4 kW. That’s a reduction of about 14.6 kW while still moving ~80% of the airflow (assuming similar system conditions).
| Speed setpoint | Relative flow | Relative power (≈ speed³) | Power reduction vs 100% |
|---|---|---|---|
| 90% | ~90% | ~72.9% | ~27.1% |
| 80% | ~80% | ~51.2% | ~48.8% |
| 70% | ~70% | ~34.3% | ~65.7% |
Start by identifying whether the trip is current-related, voltage-related, or signal/control-related; this narrows root cause fast and prevents random parameter changes.
| Symptom | Likely cause | Practical fix |
|---|---|---|
| Overcurrent on accel | Ramp too fast, load spike, incorrect motor data | Increase accel time, verify nameplate data, run motor ID |
| Overvoltage on decel | Regeneration from inertia, ramp too fast | Increase decel time or add braking resistor/regenerative unit |
| Motor heats at low speed | Self-ventilation reduced, high torque demand | Add forced cooling, raise minimum speed, verify load |
| Speed hunts in PID | Aggressive gains, noisy feedback, poor filtering | Reduce P/I, filter feedback, confirm sensor scaling |
| Nuisance comms/analog faults | EMI, grounding, cable routing | Improve shielding/grounding, separate routing, add isolation |
To get consistent results from frequency drive motor control, prioritize accurate motor data, appropriate control mode, sensible ramps, and clean installation. When tuned and installed correctly, the VFD becomes a predictable process tool—not a source of intermittent trips.